Art.-Nr. RG 60-20E4

Cable tray

Cable tray, perforated, height = 60 mm, circuit integrity systems, system-specific

The perforated cable trays RG 60, designed for system-specific functional maintenance, have a side height of 60 mm and are available in widths ranging from 100 to 400 mm. The standard length is 3000 mm.

Art.-Nr.
RG 60-20E4
height
60 mm
width
200 mm
length
3000 mm
material thickness
0.80 mm
distributed load control cable
0.17 kN/m
cross section area
117 cm2
Weight per storage unit
6.400 kg
No stepping
Fire protection

Variants

Steel, pre-galvanised/Sendzimir process

Article

H

height

B

width

L

length

t

material thickness

QSK

distributed load control cable

A

cross section area

G

Weight per storage unit

  • RG 60-10S
    Cable tray
    height
    60 mm
    width
    100 mm
    length
    3000 mm
    material thickness
    0.75 mm
    distributed load control cable
    0.09 kN/m
    cross section area
    57 cm2
    Weight per storage unit
    4.300 kg
  • RG 60-20S
    Cable tray
    height
    60 mm
    width
    200 mm
    length
    3000 mm
    material thickness
    0.75 mm
    distributed load control cable
    0.17 kN/m
    cross section area
    117 cm2
    Weight per storage unit
    5.800 kg
  • RG 60-30S
    Cable tray
    height
    60 mm
    width
    300 mm
    length
    3000 mm
    material thickness
    0.75 mm
    distributed load control cable
    0.26 kN/m
    cross section area
    177 cm2
    Weight per storage unit
    7.400 kg
  • RG 60-40S
    Cable tray
    height
    60 mm
    width
    400 mm
    length
    3000 mm
    material thickness
    0.88 mm
    distributed load control cable
    0.34 kN/m
    cross section area
    237 cm2
    Weight per storage unit
    10.600 kg

Steel, hot-dip galvanised

Article

H

height

B

width

L

length

t

material thickness

QSK

distributed load control cable

A

cross section area

G

Weight per storage unit

  • RG 60-10F
    Cable tray
    height
    60 mm
    width
    100 mm
    length
    3000 mm
    material thickness
    0.75 mm
    distributed load control cable
    0.09 kN/m
    cross section area
    57 cm2
    Weight per storage unit
    4.800 kg
  • RG 60-20F
    Cable tray
    height
    60 mm
    width
    200 mm
    length
    3000 mm
    material thickness
    0.75 mm
    distributed load control cable
    0.17 kN/m
    cross section area
    117 cm2
    Weight per storage unit
    6.500 kg
  • RG 60-30F
    Cable tray
    height
    60 mm
    width
    300 mm
    length
    3000 mm
    material thickness
    0.75 mm
    distributed load control cable
    0.26 kN/m
    cross section area
    177 cm2
    Weight per storage unit
    8.300 kg
  • RG 60-40F
    Cable tray
    height
    60 mm
    width
    400 mm
    length
    3000 mm
    material thickness
    0.88 mm
    distributed load control cable
    0.34 kN/m
    cross section area
    237 cm2
    Weight per storage unit
    11.700 kg

Details

  • These articles have been tested for functional integrity in the event of fire.
  • The guidelines applicable to the specific application can be found in the relevant certificates and test reports.

Tender texts

Ausschreiben.de

Tender texts for this product

Open Link
Heinze.de

Tender texts for this product

Open Link


Downloads

    • de

    P-MPA-E-15-019 - KDU57 - Functional maintenance certificate

    General building authority test certificate
    DIN 4102-12
    Cable manufacturers: Dätwyler, Eupen, Leoni Studer, Prysmian, Nexans
    Fire resistance duration: F30; F60; F90
    Functional maintenance classes: E30; E60; F90
    Cable load: ≤ 20 kg/m
    Fastening distance: ≤ 1.5 m
    Cable types: (N)HXH, (N)HXCH, JE-H(St)H,
    Period of validity: 09.10.2026

    PDF (10.27 MB)

    DownloadDownload
    • de

    P-MPA-E-14-010 - KDU57/KDU 60 - Functional maintenance certificate

    General building authority test certificate
    DIN 4102-12
    Cable manufacturer: Kabelwerke Eupen AG
    Fire resistance duration: F30; F60; F90
    Functional maintenance classes: E30; E60; F90
    Cable load: 20 kg/m
    Fastening distance: ≤ 1.5 m
    Cable types: (N)HXH, (N)HXCH, JE-H(St)H,
    Period of validity: 23/07/2029

    PDF (4.94 MB)

    DownloadDownload
    • de

    P-MPA-E-16-013 - KDU57/KDU 60 - Functional maintenance certificate

    General building authority test certificate
    DIN 4102-12
    Cable manufacturer: Studer Cables AG
    Fire resistance duration: F30; F60; F90
    Functional maintenance classes: E30; E60; F90
    Cable load: 20 kg/m
    Fastening distance: ≤ 1.5 m
    Cable types: (N)HXH, (N)HXCH, JE-H(St)H,
    Period of validity: 30.08.2027

    PDF (7.84 MB)

    DownloadDownload
    • de

    P-MPA-E-16-007 - KDU60 - Functional maintenance certificate

    DIN 4102-12
    Cable manufacturer: Dätwyler
    Fire resistance duration: F30; F60; F90
    Functional maintenance classes: E30; E60; F90
    Cable load: ≤ 30 kg/m
    Fastening distance: ≤ 1.5 m
    Cable types: (N)HXH, (N)HXCH, JE-H(St)H,
    Validity period: 01.02.2027

    PDF (8.13 MB)

    DownloadDownload
    • de

    MPABS-2400990 - Mixes cable installations - Fire protection statement

    DIN 4102-12
    Fire resistance duration: F30; F60; F90
    Functional integrity classes: E30; E60; F90
    Period of validity: 10.06.2029

    PDF (195.29 KB)

    DownloadDownload
    • de

    2104/681/23 - Fire protection assessment

    False ceiling installation, escape route installation, MLAR, LAR
    Fire resistance duration: F30
    Fire resistance: 30 minutes
    Fastening distance: ≤ 1.5 m
    Period of validity: 18.12.2028

    PDF (5.77 MB)

    DownloadDownload
    • de

    GA-2017/068 - Expert statement

    DIN 4102-12
    Fire protection fastening on load-bearing timber components
    Fire resistance duration: F30; F60
    Functional maintenance classes: E30; E60
    Cable load: ≤ 10 kg/m, ≤ 20 kg/m, ≤ 30 kg/m
    Mounting distance: ≤ 1.5 m
    Period of validity: 22/08/2027

    PDF (1.49 MB)

    DownloadDownload
    • de

    GA-2025-036 - Mixed cable installation assembly of floor connectors - Expert statement

    DIN 4102-12
    Fire resistance duration: F30; F60; F90
    Functional integrity classes: E30; E60; F90
    Period of validity: 09.05.2030

    PDF (186.69 KB)

    DownloadDownload

Included accessories