RTR 60

Cable tray divider, height = 50 mm for escape route installation

Variants

Steel, pre-galvanised/Sendzimir process

Article

H

height

L

length

G

Weight per storage unit

Included accessories
  • RTR 60S
    Cable tray barrier strip RTR 60S
    height
    50 mm
    length
    3000 mm
    Weight per storage unit
    1.528 kg
    Included accessories

Details

  • These articles have been tested for use in escape route installations.
  • The guidelines applicable to the specific application can be found in the relevant certificates and test reports.

Tender texts

Ausschreiben.de

Tender texts for this product

Open Link
Heinze.de

Tender texts for this product

Open Link

Downloads

    • de

    P-MPA-E-14-010 - KDU57/KDU 60 - Functional maintenance certificate

    General building authority test certificate
    DIN 4102-12
    Cable manufacturer: Kabelwerke Eupen AG
    Fire resistance duration: F30; F60; F90
    Functional maintenance classes: E30; E60; F90
    Cable load: 20 kg/m
    Fastening distance: ≤ 1.5 m
    Cable types: (N)HXH, (N)HXCH, JE-H(St)H,
    Period of validity: 23/07/2029

    PDF (4.94 MB)

    DownloadDownload
    • de

    P-MPA-E-16-013 - KDU57/KDU 60 - Functional maintenance certificate

    General building authority test certificate
    DIN 4102-12
    Cable manufacturer: Studer Cables AG
    Fire resistance duration: F30; F60; F90
    Functional maintenance classes: E30; E60; F90
    Cable load: 20 kg/m
    Fastening distance: ≤ 1.5 m
    Cable types: (N)HXH, (N)HXCH, JE-H(St)H,
    Period of validity: 30.08.2027

    PDF (7.84 MB)

    DownloadDownload
    • de

    MPABS-2402543 - Fire protection statement

    DIN 4102-12
    Standardised supporting structure: Cable trays
    Fire resistance duration: F30; F60; F90
    Functional maintenance classes: E30; E60; F90
    Cable load: ≤ 10 kg/m
    Fastening distance: ≤ 1.2 m
    Period of validity: 15.01.2030

    PDF (11.03 MB)