Art.-Nr. RGV-BS 60F

Cable tray coupler, fire prevention

Cable tray side connector, height = 45 mm, maintenance of function

Art.-Nr.
RGV-BS 60F
height
45 mm
length
190 mm
Weight per storage unit
0.156 kg
Fire protection

Variants

Steel, pre-galvanised/Sendzimir process

Article

H

height

L

length

G

Weight per storage unit

Included accessories
  • RGV-BS 60S
    Cable tray coupler, fire prevention
    height
    45 mm
    length
    190 mm
    Weight per storage unit
    0.150 kg
    Included accessories

Steel, hot-dip galvanised

Article

H

height

L

length

G

Weight per storage unit

Included accessories
  • RGV-BS 60F
    Cable tray coupler, fire prevention
    height
    45 mm
    length
    190 mm
    Weight per storage unit
    0.156 kg
    Included accessories

Details


    Tender texts

    Ausschreiben.de

    Tender texts for this product

    Open Link
    Heinze.de

    Tender texts for this product

    Open Link

    Downloads

      • de

      P-MPA-E-15-019 - KDU57 - Functional maintenance certificate

      General building authority test certificate
      DIN 4102-12
      Cable manufacturers: Dätwyler, Eupen, Leoni Studer, Prysmian, Nexans
      Fire resistance duration: F30; F60; F90
      Functional maintenance classes: E30; E60; F90
      Cable load: ≤ 20 kg/m
      Fastening distance: ≤ 1.5 m
      Cable types: (N)HXH, (N)HXCH, JE-H(St)H,
      Period of validity: 09.10.2026

      PDF (10.27 MB)

      DownloadDownload
      • de

      P-MPA-E-14-010 - KDU57/KDU 60 - Functional maintenance certificate

      General building authority test certificate
      DIN 4102-12
      Cable manufacturer: Kabelwerke Eupen AG
      Fire resistance duration: F30; F60; F90
      Functional maintenance classes: E30; E60; F90
      Cable load: 20 kg/m
      Fastening distance: ≤ 1.5 m
      Cable types: (N)HXH, (N)HXCH, JE-H(St)H,
      Period of validity: 23/07/2029

      PDF (4.94 MB)

      DownloadDownload
      • de

      P-MPA-E-16-013 - KDU57/KDU 60 - Functional maintenance certificate

      General building authority test certificate
      DIN 4102-12
      Cable manufacturer: Studer Cables AG
      Fire resistance duration: F30; F60; F90
      Functional maintenance classes: E30; E60; F90
      Cable load: 20 kg/m
      Fastening distance: ≤ 1.5 m
      Cable types: (N)HXH, (N)HXCH, JE-H(St)H,
      Period of validity: 30.08.2027

      PDF (7.84 MB)

      DownloadDownload
      • de

      P-MPA-E-16-007 - KDU60 - Functional maintenance certificate

      DIN 4102-12
      Cable manufacturer: Dätwyler
      Fire resistance duration: F30; F60; F90
      Functional maintenance classes: E30; E60; F90
      Cable load: ≤ 30 kg/m
      Fastening distance: ≤ 1.5 m
      Cable types: (N)HXH, (N)HXCH, JE-H(St)H,
      Validity period: 01.02.2027

      PDF (8.13 MB)

      DownloadDownload
      • de

      GA-2017/068 - Expert statement

      DIN 4102-12
      Fire protection fastening on load-bearing timber components
      Fire resistance duration: F30; F60
      Functional maintenance classes: E30; E60
      Cable load: ≤ 10 kg/m, ≤ 20 kg/m, ≤ 30 kg/m
      Mounting distance: ≤ 1.5 m
      Period of validity: 22/08/2027

      PDF (1.49 MB)

      DownloadDownload

    Included accessories