KHA 7

Technical details

  • These articles have been tested for functional integrity in the event of fire.
  • The guidelines applicable to the specific application can be found in the relevant certificates and test reports.


Downloads

    • de

    3335-772-11-3 - Expert statement

    DIN 4102-12
    Standardised supporting structure: Cable clamps
    Fire resistance duration: F30; F60; F90
    Functional maintenance classes: E30; E60; F90
    Fastening distance: ≤ 0.3 m; ≤ 0.4 m
    Period of validity: 06.07.2027

    PDF (834.47 KB)

    DownloadDownload
    • de

    MPABS-2402543 - Fire protection statement

    DIN 4102-12
    Standardised supporting structure: Cable trays
    Fire resistance duration: F30; F60; F90
    Functional maintenance classes: E30; E60; F90
    Cable load: ≤ 10 kg/m
    Fastening distance: ≤ 1.2 m
    Period of validity: 15.01.2030

    PDF (11.03 MB)

    DownloadDownload