Wall Mounting

Vorteile


Downloads

    • de

    MPABS-2402543 - Fire protection statement

    DIN 4102-12
    Standardised supporting structure: Cable trays
    Fire resistance duration: F30; F60; F90
    Functional maintenance classes: E30; E60; F90
    Cable load: ≤ 10 kg/m
    Fastening distance: ≤ 1.2 m
    Period of validity: 15.01.2030

    PDF (11.03 MB)

    DownloadDownload
    • de

    MPABS-2402542 - Fire protection statement

    DIN 4102-12
    Standardised supporting structure: Cable ladders
    Fire resistance duration: F30; F60; F90
    Functional maintenance classes: E30; E60; F90
    Cable load: ≤ 20 kg/m
    Fastening distance: ≤ 1.2 m
    Period of validity: 15.01.2030

    PDF (4.85 MB)