Art.-Nr. RG 60-10S

Cable tray

Art.-Nr.
RG 60-10S
height
60 mm
width
100 mm
length
3000 mm
material thickness
0.75 mm
distributed load control cable
0.09 kN/m
cross section area
57 cm<sup>2</sup>
Weight per storage unit
4.300 kg

Variants

Steel, pre-galvanised/Sendzimir process

Article

H

height

B

width

L

length

t

material thickness

QSK

distributed load control cable

A

cross section area

G

Weight per storage unit

  • RG 60-10S
    Cable tray
    60 mm
    100 mm
    3000 mm
    0.75 mm
    0.09 kN/m
    57 cm2
    4.300 kg
  • RG 60-20S
    Cable tray
    60 mm
    200 mm
    3000 mm
    0.75 mm
    0.17 kN/m
    117 cm2
    5.800 kg
  • RG 60-30S
    Cable tray
    60 mm
    300 mm
    3000 mm
    0.75 mm
    0.26 kN/m
    177 cm2
    7.400 kg
  • RG 60-40S
    Cable tray
    60 mm
    400 mm
    3000 mm
    0.88 mm
    0.34 kN/m
    237 cm2
    10.600 kg

Tender texts

Ausschreiben.de

Tender text for this product

Open Link
Heinze.de

Tender text for this product

Open Link

Downloads

  • Price list Building extension 2025

    Valid from February 1st, 2025, updated version from 27/01/2025.

    PDF, 46 MB

    de en
  • P-MPA-E-15-019 - KDU57 - Functional maintenance certificate

    General building authority test certificate<br />DIN 4102-12<br />Cable manufacturers: Dätwyler, Eupen, Leoni Studer, Prysmian, Nexans<br />Fire resistance duration: F30; F60; F90<br />Functional maintenance classes: E30; E60; F90<br />Cable load: ≤ 20 kg/m<br />Fastening distance: ≤ 1.5 m<br />Cable types: (N)HXH, (N)HXCH, JE-H(St)H, <br />Period of validity: 09.10.2026

    PDF, 10 MB

  • P-MPA-E-14-010 - KDU57/KDU 60 - Functional maintenance certificate

    General building authority test certificate<br />DIN 4102-12<br />Cable manufacturer: Kabelwerke Eupen AG<br />Fire resistance duration: F30; F60; F90<br />Functional maintenance classes: E30; E60; F90<br />Cable load: 20 kg/m<br />Fastening distance: ≤ 1.5 m<br />Cable types: (N)HXH, (N)HXCH, JE-H(St)H, <br />Period of validity: 23/07/2029

    PDF, 5 MB

  • P-MPA-E-16-013 - KDU57/KDU 60 - Functional maintenance certificate

    General building authority test certificate<br />DIN 4102-12<br />Cable manufacturer: Studer Cables AG<br />Fire resistance duration: F30; F60; F90<br />Functional maintenance classes: E30; E60; F90<br />Cable load: 20 kg/m<br />Fastening distance: ≤ 1.5 m<br />Cable types: (N)HXH, (N)HXCH, JE-H(St)H, <br />Period of validity: 30.08.2027<br />

    PDF, 8 MB

  • MPABS-2402543 - Fire protection statement

    DIN 4102-12<br />Standardised supporting structure: Cable trays<br />Fire resistance duration: F30; F60; F90<br />Functional maintenance classes: E30; E60; F90<br />Cable load: ≤ 10 kg/m<br />Fastening distance: ≤ 1.2 m<br />Period of validity: 15.01.2030

    PDF, 11 MB


Included accessories